Duplex Sump Pump Controller , Water Pump Motor Controller Short Circuit Protection


Product Details:

Certification: CE
Model Number: L932
Packaging Details: Carton

Detailed Product Description

Phase: Three Phase Pump Controlled Quantity: Two Pumps
Enclosure Protection Grade: IP54 Install Position: Wall Mounting
Displaying :: LCD Display Liquid Level Transfer Distance: ≤1000m

Digital Three Phase Water Pump Control Panel – Auto And Manual,00.75-15KW ,With One Button Calibration.

Products Brief :

L932 is applied for automatic liquid level control / pressure control and effective protection for duplex pumps of with AC380V, 50hz, single phase output power 0.75KW-15KW (1HP-20HP),direct start, including stainless steel or cast iron submersible pump,centrifugal pump, sewage pump etc.
Model L932 has many operation modes by adopting different electric installations. An important feature that makes the difference between Model L932 and common On/Off pump control box is the probe / sensor free in the well. Our special design makes it a very reliable and sensitive Protection against pump dry run without installation probe / sensor in the well.
Model L932 is useful in all cases we need to control and protect single pump managing its turn-on and turn off by different electric installations.

Main Technical Specifications
■Rated Input Voltage…………………………………………………AC380V / Three Phase
■ Rated Frequency…………………………………………50Hz-60Hz (at option)
■ Rated Output Power of Motor…………………0.75-4KW / 5.5-11KW/15KW(at option)
■ Open Phase Trip Response Time…….……………………2sec
■ Short Circuit Trip Response Time……………………………………………0.1sec
■ Dry Running Trip Response Time………………………………………………6sec
■ Over / Under Voltage Trip Response Time……………………………………5sec
■ Pump Stalled Trip Response Time……………………..………0.5sec
■ Over Current Trip Response Time……………………………………5sec-5min
■ Recovery Time of Over / Under Voltage……………………………………2min
■ Recovery Time of Over Current…………………………………………30min
■ Recovery Time of Dry Running.………………………………………………30min
■ Over / Under Voltage Trip……..……………………………….………………±15%
■ Dry Running Trip……………………………………………….70%
■ Pump Stalled Trip………………………………………….……………………200%

① the Characteristic of Inverse-time, the stronger of the current, The shorter of trip response time)
② Percent of rated input voltage ( i.e if the rated input voltage is 380V, the Over voltage trip is 437V, the Under voltage trip is 323V)
③ Percent of load time of calibration ( i.e if the running ampere of pump motor is 10A during the calibration, the dry running trip ampere is 7A)
④ Percent of load time of calibration ( i.e if the running ampere of pump motor is 10A during the calibration, The pump stalled trip ampere is 20A)

Model L932
Main technical data
Start type Direct on line
Qty of controlled pump Two pumps
Rated input voltage: AC380V Single phase
50HZ/ 60HZ
Rated output power: 0.75KW-15KW (1HP-20HP)
Capacitor: N/M
Protection Offered: Dry run
Over load
Transient surge
Under voltage
Over voltage
Open phase
Pump shaft rust protection
Pump stalled
Short circuit
Over temp
Three phase unbalance
Phase reversal
Repeated start
Application & Control characteristic Control and protect universal pump
Using water level sensor or float switch to control pump start and stop
Applied for water supply by liquid level control through float switch or liquid probe
Applied for water supply by pressure control through pressure switch and pressure tank
Applied for drainage by liquid level control through float switch or liquid probe
Other features Push button calibration
Memory function when power off & recoveryInteractive LCD Screen
Main installation data
Working temperature
Working humidity
Degree of protection
Install position
Unit dimension (L x W x H)
-25℃– +55℃
20%–90%RH, no drips concreted
IP22
Wall mounting
1 70× 1 55× 8.5mm
Phase

Three