0.37-2.2KW Booster Pump Controller With Pressure Transmitter 0.5-4.5V


Product Details:

Certification: CE
Model Number: L922-B
Packaging Details: carton

Detailed Product Description

Phase: Single Phase Pump Controlled Quantity: One Pump
Enclosure Protection Grade: IP54 Install Position: Wall Mounting
Displaying :: LCD Display

ntelligent Single Phase Duplex Booster Pump Controller– Auto And Manual,0.37-2.2KW

Model: L922-B

Products Brief :

Model L922-B is specially designed for pressure booster pumping system, by adopting pressure transmitter (0.5-4.5V), pump user can easily set the different pressure value and observe the dynamic pressure value in the pipeline.

Typical usage scenarios include:
– Houses – Flats
– Holidays houses – Farms
– Water supply from wells – Industrial plants

Main Technical Specifications
Rated Input Voltage…………………………………………………AC220V / Single Phase
■ Rated Frequency………………………………………………….……50Hz-60Hz (at option)
■ Rated Output Power of Motor……………………………0.37-2.2KW / 3-4KW(at option)
■ Short Circuit Trip Response Time……………………………………………………0.1sec
■ Dry Running Trip Response Time…………………………………………………… 6sec
■ Over / Under Voltage Trip Response Time……………………………………….….5sec
■ Pump Stalled Trip Response Time……………………..………………………………0.5sec
■ Over Current Trip Response Time………………………………………………5sec-5min
■ Recovery Time of Over / Under Voltage………………………………………..…….…2min
■ Recovery Time of Over Current…………………………………………………….…30min
■ Recovery Time of Dry Running.………………………………………………….…30min
■ Over / Under Voltage Trip……..……………………………….………………….….…±15%
■ Dry Running Trip……………………………………………….………………….…….….70%
■ Pump Stalled Trip………………………………………….……………………………..200%

①the Characteristic of Inverse-time, the stronger of the current, The shorter of trip response time)
② Percent of rated input voltage ( i.e if the rated input voltage is 220V, the Over voltage trip is
253V, the Under voltage trip is 187V)
③ Percent of load time of calibration ( i.e if the running ampere of pump motor is 6A during the
calibration, the dry running trip ampere is 4.2A)
④ Percent of load time of calibration ( i.e if the running ampere of pump motor is 6A during the calibration, The pump stalled trip ampere is 12A)

Application Control & protect booster pump only
Model L922-B
Main technical data
.Start type Direct on line
. Qty of controlled pump Duplex pump
. Rated input voltage: AC220V-240V Single phase
50HZ/ 60HZ
. Rated output power: 0.37kw-2.2kw (0.5hp-3hp)
3-4kw(4hp-5.5hp)
Protection function Over load protection
Pump stalled protection
Dry run protection
Under voltage protection
Over voltage protection
Repeat start protection
Control characteristic Connecting 0.5-4.5V pressure transmitter to replace pressure switch
Duplex pump control
.Main pump / standby pump automatically alternate
.Main pump / standby pump automatically switch against malfunction
.Standby pump participate running if required
Other features LCD screen displaying dynamic real time pressure value & pump running status
Pump accumulative running time recording
Pump last five faults record displaying
Presenting one dry contact point (BA port)
Present RS485 port
Present user remote monitor
LCD screen locked function under Auto state
Push button calibration
Main installation data
Working temperature
Working humidity
Degree of protection
Install position
Unit dimension (L x W x H)
-25℃– +55℃
20%–90%RH, no drips concreted
IP54
Wall mounting
310 x 220x 1 20mm
Phase

Single