Detailed Product Description
Phase: | Three Phase | Pump Controlled Quantity: | Two Pumps |
---|---|---|---|
Enclosure Protection Grade: | IP54 | Install Position: | Wall Mounting |
Displaying :: | LCD Display | Liquid Level Transfer Distance: | ≤1000m |
Digital Three Phase Water Pump Control Panel – Auto And Manual,00.75-15KW ,With One Button Calibration.
Products Brief :
L932 is applied for automatic liquid level control / pressure control and effective protection for duplex pumps of with AC380V, 50hz, single phase output power 0.75KW-15KW (1HP-20HP),direct start, including stainless steel or cast iron submersible pump,centrifugal pump, sewage pump etc.
Model L932 has many operation modes by adopting different electric installations. An important feature that makes the difference between Model L932 and common On/Off pump control box is the probe / sensor free in the well. Our special design makes it a very reliable and sensitive Protection against pump dry run without installation probe / sensor in the well.
Model L932 is useful in all cases we need to control and protect single pump managing its turn-on and turn off by different electric installations.
Main Technical Specifications
■Rated Input Voltage…………………………………………………AC380V / Three Phase
■Rated Frequency…………………………………………50Hz-60Hz (at option)
■Rated Output Power of Motor…………………0.75-4KW / 5.5-11KW/15KW(at option)
■Open Phase Trip Response Time…….……………………2sec
■Short Circuit Trip Response Time……………………………………………0.1sec
■Dry Running Trip Response Time………………………………………………6sec
■Over / Under Voltage Trip Response Time……………………………………5sec
■Pump Stalled Trip Response Time……………………..………0.5sec
■Over Current Trip Response Time……………………………………5sec-5min
■Recovery Time of Over / Under Voltage……………………………………2min
■Recovery Time of Over Current…………………………………………30min
■Recovery Time of Dry Running.………………………………………………30min
■Over / Under Voltage Trip……..……………………………….………………±15%
■Dry Running Trip……………………………………………….70%
■Pump Stalled Trip………………………………………….……………………200%
â‘ the Characteristic of Inverse-time, the stronger of the current, The shorter of trip response time)
â‘¡ Percent of rated input voltage ( i.e if the rated input voltage is 380V, the Over voltage trip is 437V, the Under voltage trip is 323V)
â‘¢ Percent of load time of calibration ( i.e if the running ampere of pump motor is 10A during the calibration, the dry running trip ampere is 7A)
â‘£ Percent of load time of calibration ( i.e if the running ampere of pump motor is 10A during the calibration, The pump stalled trip ampere is 20A)
Model | L932 |
Main technical data | |
Start type | Direct on line |
Qty of controlled pump | Two pumps |
Rated input voltage: | AC380V Single phase 50HZ/ 60HZ |
Rated output power: | 0.75KW-15KW (1HP-20HP) |
Capacitor: | N/M |
Protection Offered: | Dry run Over load Transient surge Under voltage Over voltage Open phase Pump shaft rust protection Pump stalled Short circuit Over temp Three phase unbalance Phase reversal Repeated start |
Application & Control characteristic | Control and protect universal pump Using water level sensor or float switch to control pump start and stop Applied for water supply by liquid level control through float switch or liquid probe Applied for water supply by pressure control through pressure switch and pressure tank Applied for drainage by liquid level control through float switch or liquid probe |
Other features | Push button calibration Memory function when power off & recoveryInteractive LCD Screen |
Main installation data | |
Working temperature Working humidity Degree of protection Install position Unit dimension (L x W x H) |
-25℃– +55℃ 20%–90%RH, no drips concreted IP22 Wall mounting 1 70× 1 55× 8.5mm |