Detailed Product Description
Rated Output Power: | 0.37KW-2.2KW (0.5HP-3HP) | Rated Input Voltage: | AC220V/50HZ Single Phase |
---|---|---|---|
Trip Response Time Of Over Load: | 5sec-5min | Trip Response Time Of Short Circuit: | <0.1sec |
Trip Response Time Of Under / Over Voltage: | <5sec | Trip Response Time Of Dry Run: | 6sec |
Recovery Time Of Over Load: | 30min | Recovery Time Of Under / Over Voltage: | 5min |
Recovery Time Of Dry Run: | 30min | Trip Voltage Of Over Voltage: | 253V |
Trip Voltage Of Under Voltage: | 175V |
Intelligent Single Phase Sewage Pump Controller – Auto And Manual,0.37-2.2KW
Model: L922-S
Products Brief :
Model L922/S is specially designed for sewage pumping system, by adopting level transmitter with 0.5-4.5V analog signal, pump user can easily set the different liquid depth for sewage pump operation and observe the dynamic liquid depth in the sump or sewage tank.
Typical usage scenarios include:
– Houses - Flats
– Holidays houses - Farms
– Industrial plants - Construction site
Main Technical Specifications
Rated Input Voltage…………………………………………………AC220V / Single Phase
■ Rated Frequency………………………………………………….……50Hz-60Hz (at option)
■ Rated Output Power of Motor……………………………0.37-2.2KW / 3-4KW(at option)
■ Short Circuit Trip Response Time……………………………………………………0.1sec
■ Dry Running Trip Response Time…………………………………………………… 6sec
■ Over / Under Voltage Trip Response Time……………………………………….….5sec
■ Pump Stalled Trip Response Time……………………..………………………………0.5sec
■ Over Current Trip Response Time………………………………………………5sec-5min
■ Recovery Time of Over / Under Voltage………………………………………..…….…2min
■ Recovery Time of Over Current…………………………………………………….…30min
■ Recovery Time of Dry Running.………………………………………………….…30min
■ Over / Under Voltage Trip……..……………………………….………………….….…±15%
■ Dry Running Trip……………………………………………….………………….…….….70%
■ Pump Stalled Trip………………………………………….……………………………..200%
① the Characteristic of Inverse-time, the stronger of the current, The shorter of trip response time)
② Percent of rated input voltage ( i.e if the rated input voltage is 220V, the Over voltage trip is
253V, the Under voltage trip is 187V)
③ Percent of load time of calibration ( i.e if the running ampere of pump motor is 6A during the
calibration, the dry running trip ampere is 4.2A)
④ Percent of load time of calibration ( i.e if the running ampere of pump motor is 6A during the calibration, The pump stalled trip ampere is 12A)
Application | Control & protect sewage / drainage pump only |
Model | L922-S |
Main technical data | |
.Start type | Direct on line |
. Qty of controlled pump | Duplex pump |
. Rated input voltage: | AC220V-240V Single phase 50HZ/ 60HZ |
. Rated output power: | 0.37kw-2.2kw (0.5hp-3hp) 3-4kw(4hp-5.5hp) |
Protection function | Over load protection Pump stalled protection Dry run protection Under voltage protection Repeat start protection |
Control characteristic | Connecting 0.5-4.5V level transmitter to replace float switch or level probe Duplex pump control .Main pump / standby pump automatically alternate .Main pump / standby pump automatically switch against malfunction .Standby pump participate running if required |
Other features | LCD screen displaying dynamic real time depth & pump running status Pump shaft anti-rusty Pump accumulative running time recording Pump last five faults recording displaying Presenting one dry contact point (BA port) Present RS485 port Present user remote monitor LCD screen locked function under Auto state Push button calibration |
Main installation data | |
Working temperature Working humidity Degree of protection Install position Unit dimension (L x W x H) |
-25℃– +55℃ 20%–90%RH, no drips concreted IP54 Wall mounting 310 x 220x 1 20mm |